"16.9.11.5, System Subdivision - Floor/Zone Control Valves.
Individual floor/zone control valves shall be used at the riser at each floor for connections to piping serving floor areas in excess of 5,000 square feet."
"16.11.2.1.1 Single Tenant Occupancies.
When a fire alarm system is not required by IFC, Section 907.2, an approved audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of the building, in a normally occupied location, to alert the occupants of the fire sprinkler system activation."
"16.11.2.1.2 Multi-Tenant Occupancies.
When a fire alarm system is not required by IFC, Section 907.2, an approved audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of each tenant space, in a normally occupied location, to alert the occupants of the fire sprinkler system activation."
"16.11.2.1.3 Exterior Waterflow Alarm.
An approved audible/visual waterflow alarm (horn/strobe) shall be provided on the exterior of the building in a location approved by the AHJ."
"7.6.1 Exterior Waterflow Alarm.
When an alarm initiating device is included, an approved audible/visual waterflow alarm (horn/strobe) shall be provided on the exterior of the building in a location approved by the AHJ."
"7.6.2 Interior Alarm.
When an alarm initiating device is included, an interior fire alarm notification appliance is also required to sound throughout the dwelling. An approved audible sprinkler flow alarm to alert the occupants of the dwelling in a normally occupied location when the flow switch is activated must be provided."
"6.8.11 Floor/Zone Control Valves.
Individual floor/zone control valves shall be used at the riser at each floor for connections to piping serving floor areas in excess of 5,000 square feet or arranged in a manner acceptable to the AHJ."
"6.16.1.1 Local Waterflow Alarms.
When a fire alarm system is not required by IFC, Section 907.2, an approved notification appliance indicating waterflow shall be provided in the interior of each residential unit/tenant space, in a normally occupied location, to alert the occupants of the fire sprinkler system activation."
"6.16.1.2 Exterior Waterflow Alarm.
An approved audible/visual waterflow alarm (horn/strobe) shall be provided on the exterior of the building in a location approved by the AHJ."
NFPA 25, Section 5.3.4.4.1, the first line is deleted and replaced with the following:
"For system antifreeze installed prior to July 1, 2023, listed antifreeze shall not be required, where all of the following conditions are met:"
NFPA 72, a new Section 18.1.1.1 is added as follows:
"The fire code official may modify the requirements of this chapter in areas of educational occupancies used exclusively for special education students."
Utah Code § 15A-5-304