The following is adopted as an amendment to the IECC to be applicable statewide:
"Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole-house mechanical ventilation, the air handler shall be powered by an electronically commutated motor."
"TABLE R403.6.2"
"MECHANICAL VENTILATION SYSTEM FAN EFFICACY"
FAN LOCATION | AIR FLOW RATE MINIMUM (CFM) | MINIMUM EFFICACY (CFM/WATT) | AIR FLOW RATE MAXIMUM (CFM) |
HRV or ERV | Any | 1.2 cfm/watt | Any |
Range hoods | Any | 2.8 cfm/watt | Any |
In-line fan | Any | 2.8 cfm/watt | Any |
Bathroom, utility room | 10 | 1.4 cfm/watt | [LESS THAN]90 |
Bathroom, utility room | 90 | 2.8 cfm/watt | Any" |
Equipment Type | SEER2/SEER | EER2/EER4 | HSPF2/HSPF |
Ductless Systems | 1.00 | 1.00 | 0.90 |
Ducted Split System | 0.95 | 0.95 | 0.85 |
Ducted Packaged System | 0.95 | 0.95 | 0.84 |
Small Duct High Velocity System | 1.00 | Not applicable | 0.85 |
Ducted Space-Constrained Air Conditioner | 0.97 | Not applicable | Not applicable |
Ducted Space-Constrained Heat Pump | 0.99 | Not applicable | 0.85" |
Utah Code § 15A-3-701