"TABLE R301.2 (3) | |||
GROUND SNOW LOADS FOR SELECTED LOCATIONS IN UTAH | |||
City/Town | County | Ground Snow Load (lb/ft2) | Elevation (ft) |
Beaver | Beaver | 35 | 5886 |
Brigham City | Box Elder | 42 | 4423 |
Castle Dale | Emery | 32 | 5669 |
Coalville | Summit | 57 | 5581 |
Duchesne | Duchesne | 39 | 5508 |
Farmington | Davis | 35 | 4318 |
Fillmore | Millard | 30 | 5138 |
Heber City | Wasatch | 60 | 5604 |
Junction | Piute | 27 | 6030 |
Kanab | Kane | 25 | 4964 |
Loa | Wayne | 37 | 7060 |
Logan | Cache | 43 | 4531 |
Manila | Daggett | 26 | 6368 |
Manti | Sanpete | 37 | 5620 |
Moab | Grand | 21 | 4029 |
Monticello | San Juan | 67 | 7064 |
Morgan | Morgan | 52 | 5062 |
Nephi | Juab | 39 | 5131 |
Ogden | Weber | 37 | 4334 |
Panguitch | Garfield | 41 | 6630 |
Parowan | Iron | 32 | 6007 |
Price | Carbon | 31 | 5558 |
Provo | Utah | 31 | 4541 |
Randolph | Rich | 50 | 6286 |
Richfield | Sevier | 27 | 5338 |
St. George | Washington | 21 | 2585 |
Salt Lake City | Salt Lake | 28 | 4239 |
Tooele | Tooele | 35 | 5029 |
Vernal | Uintah | 39 | 5384 |
Note: To convert lb/ft2 to kN/m2, multiply by 0.0479. To convert feet to meters, multiply by 0.3048.
R311.7.5.2 Tread depth. The minimum tread depth shall be 9 inches (228 mm). The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the tread's leading edge. The greatest tread depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). Winder treads shall have a minimum tread depth of 10 inches (254 mm) measured as above at a point 12 inches (305 mm) from the side where the treads are narrower. Winder treads shall have a minimum tread depth of 6 inches (152 mm) at any point. Within any flight of stairs, the greatest winder tread depth at the 12-inch (305 mm) walk line shall not exceed the smallest by more than 3/8 inch (9.5 mm).
R311.7.5.3 Nosing. The radius of curvature at the leading edge of the tread shall be no greater than 9/16 inch (14.3 mm). A nosing not less than 3/4 inch (19 mm) but not more than 1 1/4 inches (32 mm) shall be provided on stairways with solid risers. The greatest nosing projection shall not exceed the smallest nosing projection by more than 3/8 inch (9.5 mm) between two stories, including the nosing at the level of floors and landings. Beveling of nosing shall not exceed 1/2 inch (12.7 mm). Risers shall be vertical or sloped from the underside of the leading edge of the tread above at an angle not more than 30 degrees (0.51 rad) from the vertical. Open risers are permitted, provided that the opening between treads does not permit the passage of a 4-inch diameter (102 mm) sphere.
Exceptions.
"R328.12 Signage. A sign located on the exterior of the dwelling shall be installed at a location approved by the authority having jurisdiction which identifies the battery chemistry included in the ESS. This sign shall be of sufficient durability to withstand the environment involved and shall not be handwritten."
Utah Code § 15A-3-202