53 Pa. Stat. § 4635

Current through Pa Acts 2024-53, 2024-56 through 2024-111
Section 4635 - Ventilation of traps and soil lines-Wall hung water closets

Traps shall be protected from syphonage or air pressure by special vent-pipes. Traps should not be more than approximately 24 inches from the vertical line serving the trap, and of a size not less than the following tables:--

Maximum Developed Length in Feet.

Number of 1 1/2 inch Traps Vented or Equivalent

Size of Pipe.

Mains.

Branch.

Main Vertical.

1 1/4 inch vent,

20,

1

1 1/2 inch vent,

40,

2 or less,

2 inch vent,

65,

10 or less,

20 or less.

2 1/2 inch vent,

100,

20 or less,

40 or less.

3 inch vent,

10 or more stories

60 or less,

100 or less.

The branch vent-pipes shall be not less than the following sizes:--

One and one-fourth inches in diameter, for one and one-fourth inch traps.

One and one-half inches in diameter, for one and one-half inch to two and one-half inch traps.

Two inches in diameter, for three inch to four inch traps.

One-half their diameter, for traps five inches and over.

Where two (2) or more water-closets are placed side by side on a horizontal branch, the branch line shall have a relief extended as a loop vent. A pipe two (2) inches in diameter will be sufficient as a loop vent for two (2) closets. A pipe three (3) inches in diameter shall be used as a relief for three (3) or four (4) closets; and where more than four (4) closets are located on the same branch the relief shall not be less than four (4) inches in diameter. All house or building drains and soil lines on which a water-closet is located must have a three-inch main vent line. Where an additional closet is located in the cellar or basement, and within ten feet of main soil or vent line, no relief vent will be required for said closet; but where it is more than ten feet, a two inch vent line will be required as for first floor closets. Relief vent pipes for water-closets must not be less than two inches in diameter, for a length of forty feet, and not less than three inches in diameter, for more than forty feet.

Wall-Hung Water-Closets. The three inch vent stack for a single wall-hung closet must be directly back of the closet, or have a separate two inch vent. Where two wall-hung closets are placed side by side on a horizontal branch, each must have a separate two inch vent back of each closet. Where three or more wall-hung closets are placed side by side on a horizontal branch, the branch line must have a relief extended as a loop vent. A pipe three inches in diameter shall be used as relief for three or four wall-hung water-closets, in addition to the separate two inch vent directly back of each closet. Where more than four closets are located on the same branch, the relief must be four inches in diameter, in addition to the separate two inch vent directly back of each closet.

No revent from traps under bell-traps will be required. Connections between P traps and bell-traps should be made as hereinbefore provided.

Any building having a sewer connection with a public or private sewer used for bell-trap connections or floor drainage only, a two-inch relief line must be extended to the roof of building from rear end of main drain. House or building drains, constructed for roof drainage only, will not require a relief vent.

A floor-trap for a shower shall be vented. If the number of these fixtures on a branch is two (2) or more, the waste line shall be extended as a loop vent, instead of back venting the separate traps; and when located in basement floor, they shall be provided with a removable strainer or cleanout.

Back vent pipes, from traps above the floor, must either be connected with crown of trap with ground in brass coupling, or, if connected solidly to trap, must have a ground in brass coupling at wall.

53 P.S. § 4635

1901, June 7, P.L. 493, No. 245, § 35. Amended 1909, May 14, P.L. 840, § 7; 1937, March 31, P.L. 168, § 1.