053-7 Wyo. Code R. § 7-2

Current through April 27, 2019
Section 7-2 - Anchoring and Guy Wires

(a) Every rig shall be equipped with the number and size of guy wires as recommended by the manufacturer. In the case of truck or trailer mounted rigs where no manufacturer's recommendations are made, appropriate guy wires shall be used. Exception: This rule does not apply when the manufacturer does not recommend the use of wind guys and the following conditions are met:

  • (i) no one is in the mast during operation,
  • (ii) no drill pipe, casing, etc. is racked in the mast,
  • (iii) outriggers are utilized, and
  • (iv) the mast height is sixty (60) feet or less.

(b) Every guy wire recommended by the manufacturer shall be utilized according to the manufacturer's specifications.

(c) Where the number, size and utilization of guy wires are recommended by the derrick manufacturer, anchors shall be used to secure the guy wires, except when other means or methods of anchoring the guy wires are recommended by the manufacturer which are at least as effective as these Rules and Regulations.

  • (i) Expanding anchors, pipe anchors, concrete anchors, or other approved techniques shall be used, except that temporary, moveable, or driven stakes shall not be used.
  • (ii) Anchor placement and pull test.
    • (A) With respect to anchors installed, reinstalled or relocated on or before September 24, 1970 anchors shall be proof-tested along an angle that approximates the wind guys working plane within twelve (12) months prior to the use of the anchors. Such tests will be made at the poundage determined by the anchors location (per Figure 2a) within sector A, B, or C, and computed according to the appropriate sector curve on Figure I. If either of the two (2) front anchors falls in a sector which requires a higher test pull, both front anchors shall be tested as if they were located in the sector requiring the higher pull test. If ground is frozen at the time of the test and anchors are to be used again when the ground is not frozen, the anchors must be retested before use. If any anchor is more than three (3) feet above or below the well ground level, Figure 3 shall be used to determine the adjusted distance for which the pull test requirement will be established using Figure 2a. Anchors to be used for singles derricks only shall be proof tested to 10,000 pounds and shall be located within sector A, B or C of Figure 2a.
    • (B) With respect to anchors installed, reinstalled or relocated from and after September 25, 1970, anchors shall be proof tested along an angle that approximates the wind-guys working plane within twelve (12) months prior to the use of the anchors. Such tests will be made at the poundage determined by the anchors location (per Figure 2b) within sector A, B or C, and computed according to the appropriate sector curve on Figure 1. If any anchor falls in a sector which requires a higher test pull, all four (4) anchors shall be tested as if they were located in the sector requiring the higher pull test. If ground is frozen at the time of the test and anchors are to be used again when the ground is not frozen, the anchors must be retested before use. If any anchor is more than three (3) feet above or below the well ground level, Figure 3 shall be used to determine the adjusted distance for which the pull test requirements will be established using Figure 1. Anchors to be used for singles derricks only shall be proof tested to 10,000 pounds and shall be located within sector A, B or C of Figure 2b.
  • (iii) Each well site shall have available a such well site in an accessible weatherproof container an anchor record. Such anchor record shall state whether the anchor was installed prior or subsequent to September 24, 1970, the date of any relocation or reinstallation of any anchor at the well site after September 24, 1970, each anchors pull test (sector) from Figure 2a or 2b, and the date, amount of such pull test, and identification of the tester.
    • (A) Each anchor shall be pulled and held for a period of two (2) minutes after all movement (creep) has stopped.
    • (B) The anchor record shall state "FOR SINGLES DERRICKS ONLY" if the anchors are only tested to 10,000 pounds.

CLARIFICATION OF SECTIONS 2.(c) (ii) and 2.(c) (iii)

Individual anchors installed, reinstalled or relocated prior to September 25, 1970 will be tested in accordance with Section 2,(c) (ii) (A) and Figure 2a. Individual anchors installed, reinstalled or relocated September 25, 1970, or later, will be installed and tested in accordance with Section 2.(c) (ii)(B) and Figure 2b. This means that the installation of a single anchor subsequent to September 25, 1970, would not require the remaining anchors at the same well site to be tested and installed according to Section 2.(c) (2)(B) and Figure 2b, until such anchor(s) has been installed, reinstalled or relocated. If there is any doubt that individual anchors were installed before September 25, 1970, such anchor's record will indicate this information, and will be tested in accordance with Section 2.(c)(ii) Figure 2b.

  • (iv) No derrick shall be rigged up on a work site unless the anchors have been installed and tested in accordance with this subsection.
  • (v) All anchor testing units shall be certified by the State of Wyoming Workers' Safety OSHA Division.
  • (vi) Guy wire anchors and drilling unit placement.
    • (A) Guy wire anchors shall be positioned in accordance with Figure 2a or 2b of this Chapter.
    • (B) The well operator shall provide a visible marker in such a position that a straight line through the marker and through the well head will form an angle with a line through any anchor and the well head which complies with the minimum angle requirements as follows:

      *Minimum Angle Distances From Well Centerline

      Sector

      Each Quadrant

      Minimum Angle

      Front & Rear

      Sides

      A

      20E

      35°

      14

      10

      B

      30°

      30°

      17

      10

      C

      45°

      22.5°

      24

      10

      *In the use of Figure 2b, if any anchor in the pattern falls within Sector "C", the minimum angle on all anchors is 22.5°. One or more anchors located in Section "B", with the remaining anchors in Sector "A", requires the minimum angle to be 30° on all anchors. In the use of Figure 2a, the minimum angle of any anchor is 22.5°. A field determination of the minimum angle can be found by measuring these distances in convenient units such as feet, yards or paces in reference to the well centerline, the anchors and the longitudinal axis of the unit. (Example: With a single anchor in the pattern located in Sector "C", a person could take twenty four (24) paces from the well head on an imaginary line which bisects the two (2) adjacent anchors between which the unit will be placed. At this point there would be placed a marker or a stake. He would then take ten (10) paces to the left and turn so he was aligned with the well head. If anchors "A" and "C" (Diagram A) are "outside" his alignment, these anchors would be satisfactory. Going back to the center marker, he would repeat this procedure to the right. If anchors "B" and "D" are outside his alignment, the center marker is satisfactory. If alignment to either the left or right was not satisfactory, the center marker or stake would be moved to the left or right as needed and the alignment rechecked until the center marker is located properly.)

      • (I) The visible marker shall be placed on a direct line from the well head which passes through the center marker at least 100 feet from the head.
    • (C) The drilling unit operator shall center his unit in line with the marker and the well head.
    • (D) Where there is provided a readily visible and clearly defined pad for the positioning of the unit which will maintain the required minimum angle from the longitudinal axis of the unit and well to any anchor, the use of the marker in Section 2.(c) (vi)(A)of this Chapter is optional.
  • (vii) Guy wires shall not be any closer than ten (10) feet from power lines, and in no case shall a guy wire be extended above or below a power line.
  • (viii) Installation, testing and maintenance of guy wire anchors shall be the responsibility of the party issuing the contract for the drilling.
  • (ix) All chains, boomers, clamps and tensioning devices that will remain in the working guy line shall have as much strength as the guy line. Those chains, boomers, clamps and tensioning devices not of sufficient strength shall be bypassed by continuing the guy line through or around the anchor, then back to the guy line again. The guy line shall be properly secured with at least three (3) U-bolt clamps of proper size, or their equivalent.
    • (A) A fairlead (sheave) may be attached to the eye of the anchor and used to pass the wind guy back to itself.
  • (x) A thorough inspection of all guy wires in use shall be made at least once a year and shall be visually inspected prior to each rig-up, and a full written, dated and signed report of the guy lines' conditions kept at the rig where readily available for inspection by department personnel. All inspections shall be performed by a competent person authorized by the employer to perform such inspection. Defects such as those specified in Chapter 5, Section 6.(b)(i) through (ix) of these rules and regulations shall require the guy line(s) to be removed from service.

    Image Not Available

    (Note: Directions shown are for this example only and do not require all units to be placed in a North/South position)

    Image Not Available

    Image Not Available

    Figure 2a

    Image Not Available

    Figure 2b

    Image Not Available

    ANCHOR ELEVATION ADJUSTMENT CHART

    Directions for the use of Figure 3. After determining the elevation difference between the well bore ground level and the anchor ground level, find that difference on the chart at "Anchor Elevation Above or Below Well Ground Level". Follow that difference line horizontally until it meets the vertical line which represents the actual distance from the well head or bore to the anchor. Then follow the slanted line, either up or down as applicable, until "0" (Well Ground Level) is reached. Read vertically down and find the "Horizontal Distance From Well - Feet". This adjusted distance is then applied to Figure 1 to determine the required pull test according to the Sector in which the anchor is located. (Example: An anchor located ten (10) feet above well ground level 100 feet from the well head or well bore, using Figure 3, requires the same pull test as though it was 110 feet from the well head or well bore. An anchor fifteen (15) feet below well ground level eight (80) feet from the well head or well bore would require the same pull test as though the anchor was seventy (70) feet from the well head or well bore.)

053-7 Wyo. Code R. § 7-2