010-4 Wyo. Code R. § 4-32

Current through April 27, 2019
Section 4-32 - Gas Chlorine, Safety Requirements

(a) The following gas chlorination safety features shall be required:

  • (i) Two full-face, self-contained breathing apparatus (SCBA) or supplied air respirators that meet Occupational Safety and Health Administration (OSHA) or Mine Safety Health Administration (MSHA) standards shall be provided for protection against chlorine in the event of a leak.
    • (A) The equipment shall have:
      • (I) Sufficient capacity for the intended purpose;
      • (II) SCBA equipment shall be readily accessible at a location acceptable to local emergency planning committees or the local fire chief;
      • (III) Entry into the chlorine room shall not be permitted without the necessary safety equipment when conducting general maintenance;
      • (IV) Two persons trained in the performance of routine gas chlorination operation and emergency procedures shall be readily available during normal operating hours; and
      • (V) A written respirator program shall:
        • (1.) Be provided; and
        • (2.) Employees shall be trained in the use and ma intenance of such equipment to ensure operability and safety, according to 29 CFR 1910, Occupational Health and Safety Standards and any other applicable federal, state, or local requirements for the proper handling of gas chlorine.