Wis. Admin. Code Public Service Commission PSC 185.65

Current through November 25, 2024
Section PSC 185.65 - Accuracy requirements for meters
(1) The test flow limits for positive displacement, compound, and turbine meters shall be as follows:

Meter Size (inches)

Minimum Test

Flow

(g.p.m.)

Normal test flow

limits

(g.p.m.)

5/8

1/4

1-20

3/4

1/2

2-30

1

3/4

3-50

1 1/2

1 1/2

5-100

2

2

8-160

Compound Meters

2

1/2

2-160

3

1

4-320

4

1 1/2

6-500

6

3

10-1,000

8

4

16-1,600

10

8

32-2,300

12

14

32-3,100

Turbine Meters*

2

10

16-160

3

15

24-350

4

20

40-600

6

30

80-1400

8

50

144-2,500

10

75

224-3,800

12

100

320-5,800

16

150

400-11,500

Note: See AWWA Standards C-700 (Positive Displacement Meters), C-702 (Compound Meters), and C-701 (Turbine Meters).

Note: * See s. PSC 185.61(1).

(2) Positive displacement meters shall have a percent registration betwee n 98.5 and 101.5 within the range of normal test flow limits before being placed in service. In addition, new meters shall have a percent registration at the minimum test flow between 90 [95] and 101.5. In all other cases, the percent registration shall be between 90 and 101.5 before being placed in service. These requirements, in addition to flow, are shown in the table below.

Note: It is the intent of the commission that new meters have an accuracy limits percent between 95 and 101.5.

Summary of Test Conditions and Accuracy Requirements for Positive Displacement Meters

Maximum Rate

Intermediate Rate

Minimum Rate

Size

in.

Rate

of

Flow

Test Quantity

Accuracy Limits

Rate

of

Flow

Test Quantity

Accuracy Limits

Rate

of

Flow

Test Quantity*

Accuracy Limits Percent

gpm

Gal.

Cu. Ft.

Percent

gpm

Gal.

Cu. Ft.

Percent

gpm

Gal.

Cu. Ft.

New Meters

Repaired Meters

5/8

15

100

10

98.5-101.5

2

10

1

98.5-101.5

1/4

10

1

95-101.5

90-101.5

3/4

25

100

10

98.5-101.5

3

10

1

98.5-101.5

1/2

10

1

95-101.5

90-101.5

1

40

100

10

98.5-101.5

4

10

1

98.5-101.5

3/4

10

1

95-101.5

90-101.5

11/2

80

1.000

100

98.5-101.5

8

100

10

98.5-101.5

11/2

100

10

95-101.5

90-101.5

2

120

1.000

100

98.5-101.5

15

100

10

98.5-101.5

2

100

10

95-101.5

90-101.5

* Section PSC 185.73(3) provides that at this flow rate the test quantity may be reduced to that equivalent to one-half revolution of the test dial. For the typical 5/8-inch meter the minimum test quantity would, therefore, be 5 gal. or 1/2 cu. ft.

(3) Compound meters shall have a percent registration between 97 and 103 throughout the range of normal test flow limits. At flows within the change-over flow range, the percent registration shall not be less than 90%.
(4) Turbine meters shall have a percent registration between 97 and 103 throughout the range of normal test flow limits and a percent registration of at least 95% at the minimum test flow.
(5) For meter installations with remote reading devices the above accuracy requirements apply to the metering accuracy of the complete installation.

Wis. Admin. Code Public Service Commission PSC 185.65

CR Register, January, 1997, No. 493, eff. 2-1-97.