Section PSC 135.181 - Distribution line valves addition [49 CFR 192.181]After 49 CFR 192.181(b), insert:
(bw) The distance between the valve and the regulator or regulators shall be sufficient to permit the operation of the valve during an emergency such as a large gas leak or a fire in the station. These valves shall be in accessible locations neither closer than 25 feet nor more than 1,500 feet distant from each regulator station.Wis. Admin. Code Public Service Commission PSC 135.181
CR Register, October, 1999, No. 526, eff. 11-1-99.