Current through October 28, 2024
Section PSC 114.381 - Design [Follows NESC 381G, p. 273] (Addition) Following NESC 381G, add paragraph H to read:
H. Warning signs1. Where a padmounted transformer, switchgear, pedestal, or similar above-grade enclosure is not within a fenced or other protected area and contains live parts in excess of 600 volts, a permanent and conspicuous warning sign shall be provided on the outside of the enclosure which meets the requirements as to format and color of American National Standards Institute standard ANSI Z535.1-2011, ANSI Z535.2-2011, ANSI Z535.3-2011, ANSI Z535.4-2011, and ANSI Z535.5-2011 for safety signs.2. Electric supply equipment installed prior to July 1, 2003 shall be signed to comply with these rules or the rule in effect in 2003. Warning signs installed as replacements or installed on new facilities shall comply with the standard as prescribed in s. PSC 114.381H 1 above. The "Mr. Ouch" symbol may be used as the optional pictorial part of this sign.Wis. Admin. Code Public Service Commission PSC 114.381
Renum. PSC 114.381 from PSC 114.381H under s. 13.92(4) (b) 1, Stats., Register March 2015 No. 711, eff.4/1/2015.Amended by, CR 18-007: am. (intro.) Register February 2020 No. 770, eff. 3/1/2020