A bond not smaller than AWG No. 6 copper or equivalent shall be placed between the communication grounding electrode and the supply system neutral grounding electrode where separate electrodes are used at the structure or building being served. All separate electrodes shall be bonded together except where separation is required per Rule 097. Bonding to other systems shall not be done on or within a metering enclosure unless a means of bonding, intended for inter-system bonding, is furnished as part of the metering enclosure.
Recommendation: If water piping is used as a bonding means, care must be taken to assure that the metallic path is continuous between electrodes.
Note 1: See NEC Article 800-100(D) for corresponding NEC requirements.
Note 2: The bonding together of all separate electrodes limits potential differences between them and between their associated wiring systems.
Wis. Admin. Code Public Service Commission PSC 114.099