Section PSC 113.0807 - Meter compensation
(1) Metering equipment shall not be set "fast" or "slow" to compensate for supply transformer or line losses.
(2) Loss compensators designed to be used with meters and which accurately add iron losses, copper losses, or both may be used. The compensator shall carry a tag identifying the compensation and shall be tested when the associated meter is tested and when the associated supply equipment on lines are changed.

Wis. Admin. Code Public Service Commission PSC 113.0807

CR Register, July, 2000, No. 535, eff. 8-1-00.

See s. PSC 113.0917 which covers test requirements for transformer loss compensators.