Wis. Admin. Code Public Service Commission PSC 113.0907

Current through October 28, 2024
Section PSC 113.0907 - Methods of testing block-interval pulse-operated demand meters and pulse recorders
(1) The test of block-interval pulse-operated demand meters and pulse recorders shall include a check of the electrical and mechanical operation of the demand register or pulse recorder, an inspection of the pulse initiator and a check to determine that the demand meter resets properly.
(2) A demand meter or pulse recorder, its associated pulse initiators, relay and circuitry may be considered to be operating properly when a kilowatthour check indicates that the demand meter kilowatthours are within the required accuracy limits of the watthour meter kilowatthours.

Wis. Admin. Code Public Service Commission PSC 113.0907

CR Register, July, 2000, No. 535, eff. 8-1-00.