Note: Factory-built fireplaces shall comply with s. SPS 321.32.
Note: Products listed and labeled as complying with UL 103 - "Type HT" meet this requirement. UL 103 uses several temperature ranges for different products but only the "Type HT"-designated products have met the 2100° F testing requirement.
TABLE 323.045-A
METAL THICKNESS FOR PIPE CONNECTORS
Diameter of Connector (inches) | Sheet Gage No. | Minimum Thickness (inches) |
6 to 10 | 24 | .023 |
over 10 to 16 | 22 | .029 |
over 16 | 16 | .056 |
FIGURE 323.045-A
CONSTRUCTION USING COMBUSTIBLE MATERIAL
"A" Equals the required clearance with no protection, specified in s. SPS 323.045(4) (b).
"B" Equals the reduced clearance permitted in accordance with Table 323.045-B. The wall protection should extend far enough in each direction to make 'C' equal to 'A'.
TABLE 323.045-B
CONNECTOR CLEARANCES WITH SPECIFIED FORMS OF PROTECTION1,2,3,4
Type of Protection | Minimum Required Connector Clearances (inches) |
0.013 in. (28 gage) sheet metal spaced out a minimum of one inch. | 9 |
31/2 in. thick masonry wall spaced out a minimum of one inch and adequately tied to the wall being protected (see Note 4). | 9 |
0.027 in. (22 gage) sheet metal on one-inch mineral wool batts reinforced with wire or equivalent spaced out a minimum of one inch. | 3 |
1 Spacers and ties shall be of noncombustible material.
2 All methods of protection require adequate ventilation between protective material and adjacent combustible walls and ceilings.
3 Mineral wool batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum melting point of 1550° F.
4 If a single wall connector passes through the masonry wall there shall be at least 1/2 inch of open ventilated air space between the connector and the masonry.
TABLE 323.045-C
FLOOR MOUNTINGS FOR SOLID
FUEL-BURNING APPLIANCES
Kind of Appliance | Allowed Mounting |
(1) All forced air and gravity furnaces, steam and water boilers. or | Floors of fire-resistive construction with noncombustible flooring and surface finish, or fire-resistive arches or slabs. This construction may not have combustible material against the underside. Such construction shall extend at least 18 inches beyond the appliance on all sides. |
(2) Residential-type ranges, water heaters, fireplace stoves,room heaters and combination fireplace stove/room heaters, having less than 2 inches of ventilated open space beneath the fire chamber or base of the appliance. | These appliances shall not be placed on combustible floors. |
(3) Residential-type ranges, water heaters, fireplace stoves, room heaters and combination fireplace stove/room heaters having legs or pedestals providing 2 to 6 inches of ventilated open space beneath the fire chamber or base of the appliance. | On combustible floors when such floors are protected by 4 inches of hollow masonry, laid to provide air circulation through the masonry layer. Such masonry shall be covered with 24 gage sheet metal. The required floor protection shall extend at least 18 inches on all sides of the appliance. Noncombustible floors shall extend at least 18 inches on all sides of the appliance. |
(4) Residential-type ranges, water heaters, fireplace stoves, room heaters and combination fireplace stove/room heaters having legs or pedestals providing over 6 inches of ventilated open space beneath the fire chamber or base of the covered appliance. | On combustible floors when such floors are protected by closely spaced masonry units of brick, concrete or stone, which provide at least 2 inches of thickness. Such masonry shall be covered by or placed over a sheet of 24 gage sheet metal. The required floor protection shall extend at least 18 inches on all sides of the appliance. Noncombustible floors shall extend at least 18 inches on all sides of the appliance. |
TABLE 323.045-D
STANDARD CLEARANCES FOR
SOLID-FUEL-BURNING APPLIANCES
Type of Appliance | Above Top of Casing or Appliance. Above Top and Sides of Furnace Plenum or Bonnet (inches) Above Top of Casing or Appliance. Above Top and Sides of Furnace Plenum or Bonnet (inches) | Minimum Standard Clearances (inches) | ||
From Front | From Back | From Sides | ||
Residential Appliances Steam Boilers - 15 psi Water Boilers - 250° F max. Water Boilers - 200° F max. All Water Walled or Jacketed | 6 | 48 | 6 | 6 |
Furnaces Gravity and Forced Air | 18 | 48 | 18 | 18 |
Room Heaters, Fireplace Stoves, Combinations | 36 | 36 | 36 | 36 |
Firing Side | Opp. Side | |||
Ranges | ||||
Lined Firechamber | 30 | 36 | 24 | 18 |
Unlined Firechamber | 30 | 36 | 36 | 18 |
TABLE 323.045-EMINIMUM ALLOWABLE
APPLIANCE CLEARANCE WITH
PROTECTION 1,2,3,4,5,6
Unprotected Clearances (inches) From Table 323.045-D | |||||||||
Type of Protection | For Ceilings | For Walls | |||||||
6 | 18 | 30 | 36 | 6 | 18 | 24 | 36 | 48 | |
3 1/2 in. thick masonry wall without ventilated air space | - | - | - | - | 4 | 12 | 16 | 24 | 32 |
1/2 in. thick noncombustible insulation board over 1 in. glass fiber or mineral wool batts without ventilated air space | 4 | 12 | 20 | 24 | 3 | 9 | 12 | 18 | 24 |
0.024 in. (24 gage) sheet metal over 1 in. glass fiber or mineral wool batts reinforced with wire, or equivalent, or rear face with ventilated air space | 3 | 9 | 15 | 18 | 2 | 6 | 8 | 12 | 16 |
3 1/2 in. thick masonry wall with ventilated air space | - | - | - | - | 2 | 6 | 8 | 12 | 16 |
0.024 in. (24 gage) sheet metal with ventilated air space | 3 | 9 | 15 | 18 | 2 | 6 | 8 | 12 | 16 |
1/2 in. thick noncombustible insulation board with ventilated air space | 3 | 9 | 15 | 18 | 2 | 6 | 8 | 12 | 16 |
0.024 in. (24 gage) sheet metal with ventilated air space over 0.024 in. (24 gage) sheet metal with ventilated air space | 3 | 9 | 15 | 18 | 2 | 6 | 8 | 12 | 16 |
1 in. glass fiber or mineral wool batts sandwiched between two sheets 0.024 in. (24 gage) sheet metal with ventilated air space | 3 | 9 | 15 | 18 | 2 | 6 | 8 | 12 | 16 |
1 Spacers and ties shall be of noncombustible material. No spacers or ties shall be used directly behind appliance or conductor.
2 With all clearance reduction systems using a ventilated air space, at least two sides of the protection shall be open to provide adequate air circulation. There shall be at least one inch between the clearance reduction system and combustible walls and ceilings.
3 Mineral wool bats, blanket or board shall have a minimum density of 8 lb. per cubic foot and have a minimum melting point of 1,500° F
4 Insulation material used as part of a clearance reduction system shall have a thermal conductivity (k) of One (Btu) (in)/(Sq. ft.) (Hr.) (°F) or less. Insulation board shall be formed of noncombustible material.
5 If a single wall connector passes through a masonry wall used as a wall shield, there shall be at least 1/2 inch of open, ventilated space between the connector and the masonry.
6 Clearances in front of the loading door or ash removal door of the appliance shall not be reduced.
FIGURE 323.045-B
PROTECTION OF COMBUSTIBLE WALLS
AND FLOORS
FIGURE 323.045-C
FIGURE 323.045-D
TABLE 323.045-F
Distance of Ducts From Bonnet or Plenum (inches) | Clearance to Combustibles1 Required (inches) |
0 to 36 | 18 |
over 36 to 72 | 6 |
over 72 | 1 |
1 Clearance can be reduced in accordance with Table 323.045-B
FIGURE 323.045-E
Wis. Admin. Code Department of Safety and Professional Services SPS 323.045