Building Component | Standard Reference Design | Proposed Design |
Above-grade walls | Type: mass wall if proposed wall is mass; otherwise wood frame | As proposed |
Gross area: same as proposed | As proposed | |
U-Factor: from Table 322.31-2 | As proposed | |
Solar absorptance = 0.75 | As proposed | |
Emittance = 0.90 | As proposed | |
Basement and crawlspace walls | Type: same as proposed | As proposed |
Gross area: same as proposed | As proposed | |
U-Factor: from Table 322.31-2 with insulation layer on interior side of walls | As proposed | |
Above-grade floors | Type: wood frame | As proposed |
Gross area: same as proposed | As proposed | |
U-Factor: from Table 322.31-2 | As proposed | |
Ceilings | Type: wood frame | As proposed |
Gross area: same as proposed | As proposed | |
U-Factor: from Table 322.31-2 | As proposed | |
Roofs | Type: composition shingle on wood sheathing | As proposed |
Gross area: same as proposed | As proposed | |
Solar absorptance = 0.75 | As proposed | |
Emittance = 0.90 | As proposed | |
Attics | Type: vented with aperture = 1 ft2 per 300 ft2 ceiling area | As proposed |
Foundations | Type: same as proposed | As proposed |
Doors | Area: 40 ft2 | As proposed |
Orientation: North U-Factor: same as fenestration from Table | As proposed | |
322.31-2 | As proposed | |
Glazinga | Total areab= (a) The proposed glazing area; where the proposed glazing area is less than 18% of the conditioned floor area | As proposed |
(b) 18% of the conditioned floor area; where the proposed glazing area is 18% or more of the conditioned floor area Orientation: equally distributed to four cardinal compass orientations | As proposed | |
U-Factor: from Table 322.31-2 | As proposed | |
SHGC = 0.40 Interior shade fraction: Summer (all hours when cooling is required) = 0.70 Winter (all hours when heating is required) = 0.85 | As proposed Same as standard reference designc | |
External shading: none | As proposed | |
Skylights | U-Factor: from Table 322.31-2 | As proposed |
Thermally isolated sunrooms | None | As proposed |
Air exchange rate | Specific Leakage Area (SLA)d = 0.00036 assuming no energy recovery | For residences that are not tested, the same as the standard reference design; For residences without mechanical ventilation that are tested in accordance with ASHRAE 119, Section 5.1, the measured air exchange ratee but not less than 0.35 ACH; For residences with mechanical ventilation that are tested in accordance with ASHRAE 119, Section 5.1, the measured air exchange ratee combined with the mechanical ventilation ratef, which may not be less than 0.01 X CFA + 7.5 X (N br + 1) where: CFA = conditioned floor area N br = number of bedrooms |
Mechanical ventilation | None, except where mechanical ventilation is specified by the proposed design, in which case: Annual vent fan energy use: kWh/yr = 0.03942 X CFA + 29.565 X (N br + 1) where: CFA = conditioned floor area N br = number of bedrooms | As proposed |
Internal gains | IGain = 17,900 + 23.8 x CFA + 4,104 X N br (Btu/day per dwelling unit) | Same as standard reference design |
Internal mass | An internal mass for furniture and contents of 8 pounds per square foot of floor area | Same as standard reference design, plus any additional mass specifically designed as a thermal storage elementg but not integral to the building envelope or structure |
Structural mass | For masonry floor slabs, 80% of floor area covered by R-2 carpet and pad, and 20% of floor directly exposed to room air; | As proposed |
For masonry basement walls, as proposed, but with insulation required by Table 322.31-2 located on the interior side of the walls; | As proposed | |
For other walls, for ceilings, floors, and interior walls, wood frame construction | As proposed | |
Heating systems h,i | Fuel type: same as proposed design efficiencies: | As proposed |
Electric: air-source heat pump with prevailing federal minimum efficiency; | As proposed | |
Nonelectric furnaces: natural gas furnace in | ||
accordance with Table 322.31-3; | As proposed | |
Nonelectric boilers: natural gas boiler in accordance with Table 322.31-3; | As proposed | |
Capacity: sized in accordance with section SPS 322.40(3) | As proposed | |
Cooling systems h,j | Fuel type: electric | As proposed |
Efficiency: in accordance with prevailing federal minimum standards | As proposed | |
Capacity: sized in accordance with section SPS 322.40(3) | As proposed | |
Service Water Heating h,k | Fuel type: same as proposed design | As proposed |
Efficiency: in accordance with prevailing federal minimum standards | As proposed | |
Use: gal/day = 30 + 10 X N br | Same as standard reference | |
Tank temperature: 120°F | Same as standard reference | |
Thermal distribution systems | A thermal distribution system efficiency (DSE) of 0.80 shall be applied to both the heating and cooling system efficiencies | Same as standard reference design, except as specified by Table 322.53-2 |
Thermostat | Type: manual, cooling temperature set point = 78°F; heating temperature set point = 68°F | Same as standard reference design |
a Glazing shall be defined as sunlight-transmitting fenestration, including the area of sash, curbing or other framing elements, that enclose conditioned space. Glazing includes the area of sunlight-transmitting fenestration assemblies in walls bounding conditioned basements. For doors where the sunlight-transmitting opening is less than 50% of the door area, the glazing area is the sunlight transmitting opening area. For all other doors, the glazing area is the rough frame opening area for the door including the door and the frame.
b For residences with conditioned basements, R-2 and R-4 residences and townhouses, the following formula shall be used to determine glazing area: AF = As X FA X F where:
And where:
c For fenestrations facing within 15 degrees of true south that are directly coupled to thermal storage mass, the winter interior shade fraction may be increased to 0.95 in the proposed design.
d Where Leakage Area (L) is defined in accordance with Section 5.1 of ASHRAE 119 and where: SLA = L/CFA where L and CFA are in the same units.
e Tested envelope leakage shall be determined and documented by an independent party approved by the code official. Hourly calculations as specified in the 2005 ASHRAE Handbook of Fundamentals, Chapter 27, page 27.21, Equation 40, Sherman-Grimsrud model, or the equivalent shall be used to determine the energy loads resulting from infiltration.
f The combined air exchange rate for infiltration and mechanical ventilation shall be determined in accordance with Equation 43 of 2005 ASHRAE Handbook of Fundamentals page 27.23 and the "Whole-house Ventilation" provisions of 2005 ASHRAE Handbook of Fundamentals, page 27.18 for intermittent mechanical ventilation.
g Thermal Storage Element means a component not part of the floors, walls or ceilings that is part of a passive solar system, and that provides thermal storage such as enclosed water columns, rock beds, or phase-change containers. A thermal storage element must be in the same room as fenestration that faces within 15 degrees of true south, or must be connected to a room with pipes or ducts that allow the element to be actively charged.
h For a proposed design with multiple heating, cooling or water heating systems using different fuel types, the applicable standard reference design system capacities and fuel types shall be weighted in accordance with their respective loads as calculated by accepted engineering practice for each equipment and fuel type present.
i For a proposed design without a proposed heating system, a heating system of 90% annual fuel utilization shall be assumed for both the standard reference design and proposed design. For electric heating systems, the prevailing federal minimum efficiency air-source heat pump shall be used for the standard reference design.
j For a proposed design home without a proposed cooling system, an electric air conditioner with the prevailing federal minimum efficiency shall be assumed for both the standard reference design and the proposed design.
k For a proposed design with a non-storage-type water heater, a 40-gallon storage-type water heater with the prevailing federal minimum energy factor for the same fuel as the predominant heating fuel type shall be assumed. For the case of a proposed design without a proposed water heater, a 40-gallon storage-type water heater with the prevailing federal minimum efficiency for the same fuel as the predominant heating fuel type shall be assumed for both the proposed design and standard reference design.
TABLE 322.53-2
DEFAULT DISTRIBUTION SYSTEM EFFICIENCIES FOR PROPOSED DESIGNSa
Distribution System Configuration and Condition | Forced Air Systems | Hydronic Systems |
Distribution system components located in unconditioned space | 0.80 | 0.95 |
Distribution systems entirely located in conditioned spacec | 0.88 | 1.00 |
Proposed "reduced leakage" with entire air distribution system located in the conditioned spaced | 0.96 | - |
Proposed "reduced leakage" air distribution system with components located in the unconditioned space | 0.88 | - |
Ductless systemse | 1.00 | - |
a Default values given by this table are for untested distribution systems, which must still meet minimum requirements for duct system insulation.
b Hydronic systems means those systems that distribute heating and cooling energy directly to individual spaces using liquids pumped through closed loop piping and that do not depend on ducted, forced air flows to maintain space temperatures.
c Entire system in conditioned space means that no component of the distribution system, including the air handler unit, is located outside of the conditioned space.
d Proposed "reduced leakage" means leakage to outdoors not greater than 3 cfm per 100 ft2 of conditioned floor area and total leakage not greater than 9 cfm per 100 ft2 of conditioned floor area at a pressure differential of 0.02 inches w.g. across the entire system, including the manufacturer's air handler enclosure. Total leakage of not greater than 3 cfm per 100 ft2 of conditioned floor area at a pressure difference of 0.02 inches w.g. across the entire system, including the manufacturer's air handler enclosure, shall be deemed to meet this requirement without measurement of leakage to the outdoors. This performance shall be specified as required in the construction documents and confirmed through field-testing of installed systems as documented by an approved independent party.
e Ductless systems may have forced airflow across a coil but may not have any ducted airflows external to the manufacturer's air handler enclosure.
Wis. Admin. Code Department of Safety and Professional Services SPS 322.53