Equipment Type | Minimum Efficiency | Minimum Efficiency | Test Procedure |
Split system and single package air conditioner, air cooled | 13.0 SEER | ARI 210/240 | |
Space constrained product-air conditioner | 12 SEER | ARI 210/240 | |
Through-the-wall air conditioner, air cooled, split system | 10.9 SEER (before Jan. 23, 2010) 12.0 SEER (as of Jan. 23, 2010) | ARI 210/240 | |
Through-the-wall air conditioner, air cooled, single package | 10.6 SEER (before Jan. 23, 2010) 12.0 SEER (as of Jan. 23, 2010) | ARI 210/240 | |
Split system and single package air conditioner, water and evaporatively cooled | 12.1 SEER | ARI 210/240 | |
Split system and single package heat pump, air cooled | 13.0 SEER | 7.7 HSPF | ARI 210/240 |
Through-the-wall air conditioner and heat pump-split system | 10.9 SEER (before Jan. 23, 2010) 12.0 SEER (as of Jan. 23, 2010) | 7.1 HSPF (before Jan. 23, 2010) 7.4 HSPF (as of Jan. 23, 2010) | ARI 210/240 |
Through-the-wall air conditioners and heat pumps-single package | 10.6 SEER (before Jan. 23, 2010) 12.0 SEER (as of Jan. 23, 2010) | 7.0 HSPF (before Jan. 23, 2010) 7.4 HSPF (as of Jan. 23, 2010) | ARI 210/240 |
Space constrained products-heat pumps | 12 SEER | 7.4 HSPF | ARI 210/240 |
Water source, heating mode, 68°F entering water | 4.2 COP | ARI/ASHRAE 13256-1 | |
Groundwater source, heating mode, 50°F entering water | 3.6 COP | ARI/ASHRAE 13256-1 | |
Ground source, heating mode, 32°F entering water | 3.1 COP | ARI/ASHRAE 13256-1 |
Wis. Admin. Code Department of Safety and Professional Services SPS 322.45