Wis. Admin. Code Department of Safety and Professional Services SPS 322.45

Current through October 28, 2024
Section SPS 322.45 - Air conditioner and heat pump efficiencies
(1) Heating and cooling equipment shall meet the minimum efficiency requirements in Table 322.45 when tested and rated in accordance with the applicable test procedure.
(2) The efficiency shall be verified through certification under an approved certification program or, if no certification program exists, the equipment efficiency ratings shall be supported by data furnished by the manufacturer.
(3) Where multiple rating conditions or performance requirements are provided, the equipment shall satisfy all efficiency requirements under this chapter.
(4) Where components, such as indoor or outdoor coils, from different manufacturers are used, calculations and supporting data shall be furnished by the designer that demonstrate that the combined efficiency of the specified components meets the requirements under this section.

Equipment Type

Minimum Efficiency

Minimum Efficiency

Test Procedure

Split system and single package air conditioner, air cooled

13.0 SEER

ARI 210/240

Space constrained product-air conditioner

12 SEER

ARI 210/240

Through-the-wall air conditioner, air cooled, split system

10.9 SEER (before Jan. 23, 2010)

12.0 SEER (as of Jan. 23, 2010)

ARI 210/240

Through-the-wall air conditioner, air cooled, single package

10.6 SEER (before Jan. 23, 2010)

12.0 SEER (as of Jan. 23, 2010)

ARI 210/240

Split system and single package air conditioner, water and evaporatively cooled

12.1 SEER

ARI 210/240

Split system and single package heat pump, air cooled

13.0 SEER

7.7 HSPF

ARI 210/240

Through-the-wall air conditioner and heat pump-split system

10.9 SEER (before Jan. 23, 2010)

12.0 SEER (as of Jan. 23, 2010)

7.1 HSPF (before Jan. 23, 2010)

7.4 HSPF (as of Jan. 23, 2010)

ARI 210/240

Through-the-wall air conditioners and heat pumps-single package

10.6 SEER (before Jan. 23, 2010)

12.0 SEER (as of Jan. 23, 2010)

7.0 HSPF (before Jan. 23, 2010)

7.4 HSPF (as of Jan. 23, 2010)

ARI 210/240

Space constrained products-heat pumps

12 SEER

7.4 HSPF

ARI 210/240

Water source, heating mode, 68°F entering water

4.2 COP

ARI/ASHRAE 13256-1

Groundwater source, heating mode, 50°F entering water

3.6 COP

ARI/ASHRAE 13256-1

Ground source, heating mode, 32°F entering water

3.1 COP

ARI/ASHRAE 13256-1

Wis. Admin. Code Department of Safety and Professional Services SPS 322.45

CR 08-043: cr. Register March 2009 No. 639, eff. 4-1-09; correction in (1) made under s. 13.92(4) (b) 7, Stats., Register December 2011 No. 672.