Table 321.08
Between Dwelling And: | Distance Between Objects1 | Fire Rated Construction2,5 |
Detached garage or accessory building on same property | Less than 5 feet | 3/4-hour wall3 1/3-hour door or window3 |
Another dwelling on same property | Less than 5 feet | 3/4-hour wall4 1/3-hour door or window4 |
Detached garage, accessory building, or other dwelling on same property | 5 to 10 feet | 3/4-hour wall3 1/3-hour door or window3 |
Detached garage, accessory building, or other dwelling on same property | More than 10 feet | No requirements |
Property Lines | Less than 3 feet | 3/4-hour wall 1/3-hour door or window |
Property Lines | 3 feet or more | No Requirements |
Zero Lot Line | None | Follow sub. (2) (d) requirements |
1Distance shall be measured perpendicular from wall to wall or property line, ignoring overhangs.
2 Fire rated construction shall protect the dwelling from an exterior fire source.
3 Fire rated construction may be in either facing wall.
4 Fire rated construction shall be in both facing walls.
5 The methods for garage separation in par. (a) 1. are examples of 3/4 hour wall construction.
Note: 1/20-inch is approximately the thickness of a U.S. dime.
Note: Acceptable tests for fire rating of door assemblies include ASTM E-152, UL 10B, and NFPA 252.
Wis. Admin. Code Department of Safety and Professional Services SPS 321.08