The provisions of this section control the types, materials and installation of anchors, hangers and supports for plumbing piping.
Table 382.60
Support Spacing
Material | Maximum Horizontal Spacing (feet) | Maximum Vertical Spacing (feet) |
Acrylonitrile Butadiene Styrene (ABS) | 4 | 10 |
Brass | 10 | 10 |
Cast iron | 5a | 15 |
Copper or Copper-Alloy Pipe | 12 | 10 |
Copper or Copper-Alloy Tubing: <= 1 1/4" diameterc | 6 | 10 |
>= 1 1/2" diameterc | 10 | 10 |
Chlorinated Polyvinyl Chloride (CPVC): <= 1" diameterc | 3 | 5b |
>=11/4" diameterc | 4 | 6b |
Crosslinked Polyethylene (PEX) | 2 2/3 | 4 |
Ductile Iron | 5a | 15 |
Galvanized Steel | 12 | 15 |
Lead | Continuous | 4 |
Polybutylene (PB) | 2 ft. 8 in. | 4 |
Polyethylene (PE) | 2 | 4 |
Polypropylene (PP) | 2 | 4 |
Polyvinylidene Fluoride (PVDF) | 2 | 4 |
Polyvinyl Chloride, flexible (PVC) | 2 | 4 |
Polyvinyl Chloride (PVC) | 4 | 10 |
Stainless Steel | 12 | 15 |
a The maximum horizontal spacing for supports may be increased to 10 feet when 10-foot lengths of pipe are employed.
b Mid-story guide is to be employed.
c "[GREATER THAN OR EQUAL TO] " means greater than or equal to.
"[LESS THAN OR EQUAL TO]" means less than or equal to.
Wis. Admin. Code Department of Safety and Professional Services § SPS 382.60