Pressure relief device flow capacity shall conform to the ASME Code requirements for capacity rating.
In lieu of the expiration date, a relief valve may be used for a total of 5 years if a record is maintained of when it was installed and it was not over 2 years old at the time of installation.
Wis. Admin. Code Department of Safety and Professional Services SPS 343.44