Current through October 28, 2024
Section SPS 341.32 - Pressure gages for air receivers(1) GAGE LOCATION. Air receivers shall be equipped with an indicating pressure gage so located as to be readily visible.(2) GAGE DIAL. The dial of the pressure gage shall be graduated to approximately double the pressure at which the safety valve is set, but may not be less than one and one-half times that pressure.Wis. Admin. Code Department of Safety and Professional Services SPS 341.32
Cr. Register, February, 1988, No. 386, eff. 3-1-88.