Wis. Admin. Code Department of Safety and Professional Services SPS 327.48

Current through August 26, 2024
Section SPS 327.48 - Multiple appliance venting

Two or more listed gas-or liquid-fueled appliances may be connected to a common gravity-type flue provided the appliances are equipped with listed primary safety controls and listed shutoff devices and comply with the following requirements:

(1) The appliances shall be located in the same story, except for engineered venting systems.
(2) The appliances shall be joined at a manifold or Y-type fitting as close to the chimney as possible, unless the connector from each appliance enters a separate chimney inlet and the inlets are offset at least 12 inches vertically or the separate inlets occur at right angles to each other.

Wis. Admin. Code Department of Safety and Professional Services SPS 327.48

Adopted by, EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4/1/2018