Unless designed through structural analysis, wood frame floors shall comply with the following requirements:
Note: A saddle supports the beam on the bottom and allows for the through-connection of fasteners into the side of the beam.
Note: The tributary length is usually half the span of the joist or rafter.
Note: This 4:1 ratio means bridging is required for wood-framed floors having nominal 2X10 or deeper solid-sawn-lumber joists, to provide restraint against rotation or lateral displacement.
Note: Under ACI 318 section 7.7, the minimum cover for a 5/8-inch-diameter or smaller bolt is 1 1/2 inches.
Table 327.31-A
ALLOWABLE SPANS FOR PLYWOOD FLOOR SHEATHING CONTINUOUS OVER TWO OR MORE SPANS AND FACE GRAIN PERPENDICULAR TO SUPPORTS1
Span Rating2 | Plywood Thickness | Maximum span3 |
32/16 | 15/32", 1/2", 5/8" | 16"5 |
40/20 | 19/32", 5/8", 3/4", 7/8" | 20"4,5 |
48/24 | 23/32", 3/4", 7/8" | 24" |
1 These values apply to C-D, C-C, and Structural I and II grades only. Spans shall be limited to values shown because of possible effect of concentrated loads.
2 Span Rating appears on all panels in the construction grades listed in footnote 1.
3 Plywood edges shall have approved tongue and groove joints or shall be supported with blocking, unless 1/4 inch minimum thickness underlayment or 1 1/2 inches of approved cellular or lightweight concrete is installed or finished floor is 25/32-inch wood strip. Allowable uniform load based on deflection of 1/360 of span is 165 pounds per square foot.
4 For joists spaced 24 inches on center, plywood sheathing with Span Rating 40/20 or greater can be used for subfloors when supporting 1 1/2 inches lightweight concrete.
5 May be 24 inches if 25/32-inch wood strip flooring is installed at right angles to joists.
Table 327.31-B
MINIMUM THICKNESS FOR PLYWOOD COMBINATION SUBFLOOR-UNDERLAYMENT. PLYWOOD CONTINUOUS OVER TWO OR MORE SPANS AND FACE GRAIN PERPENDICULAR TO SUPPORTS1,2
Plywood Grade | PlywoodSpeciesGroup | Maximum Support Spacing3 | ||
16" o.c | 20" o.c | 24" o.c | ||
PanelThickness(inches) | PanelThickness(inches) | PanelThickness(inches) | ||
Sanded exterior type | 1 | 1/2 | 5/8 | 3/4 |
2 & 3 | 5/8 | 3/4 | 7/8 | |
4 | 3/4 | 7/8 | 1 | |
Underlayment C-C Plugged Sturd-I-Floor4 | All Groups | APA Rated Sheathing and APA Rated Sturd-I-Floor shall be installed consistent with their rating. |
1 Spans shall be limited to values shown, based on possible effect of concentrated loads.
2 Unsupported edges shall be tongue and groove or blocked except where 1/4 inch underlayment or 25/32-inch finish floor is used.
3 Underlayment, C-C Plugged, sanded exterior type: allowable uniform load based on deflection of L/360 span for spans 24 inches or less is 125 psf; and for spans 48 inches, 65 psf.
4 The department will accept subfloor underlayment panels such as Sturd-I-Floor which meet the requirements of APA manufacturing specifications for Sturd-I-Floor panels.
Table 327.31-C
MINIMUM THICKNESS OF FLOOR BOARDS
Minimum Net Thickness | ||
Joist Spacing | Perpendicular to Joist | Diagonal to Joist |
24" | 11/16" | 3/4" |
16" | 5/8" | 5/8" |
Wis. Admin. Code Department of Safety and Professional Services SPS 327.31
Under sub. (6), wood floor joists that are perpendicular to the foundation wall can extend beyond the foundation wall by a distance of up to the depth of the joist.