Wis. Admin. Code Department of Safety and Professional Services SPS 318.1802

Current through August 26, 2024
Section SPS 318.1802 - Vertical platform lifts
(1) RUNWAY ENCLOSURE PROVIDED.
(a) This is a department rule in addition to the requirements in ASME A18.1 sections 2.1.1.2 and 2.1.1.3: The clearance between the platform and the glazing in a fire-rated runway door shall be not more than 1 1/4 inches. The shear condition at the top of any glazing in the door shall be beveled at not less than 45 degrees.
(b) This is a department rule in addition to the requirements in ASME A18.1 section 2.1.1.7: Where the platform enclosure extends less than 79 inches above the platform, the horizontal clearance between the platform enclosure on a side not containing an entrance and the adjacent runway enclosure wall or the vertical surface of the machine tower may not exceed 4 inches. The horizontal clearance between the platform enclosure and the runway enclosure walls on either side of the machine tower may not exceed 12 inches. These maximum clearances do not apply to spaces above the machine tower or to any point more than 42 inches above the top landing.
(2) PARTIAL RUNWAY ENCLOSURE PROVIDED.
(ag) This is a department rule in addition to the requirements in ASME A18.1 sections 2.1.1.2 and 2.1.1.3: Where the lift side of the door and sill present a smooth surface located not closer than 3/8 inch and not more than 3/4 inch from the access edge of the platform floor, the clearance between the edge of the platform floor and the glazing in a fire-rated runway door may not be more than 1 1/4 inches. The shear condition at the top of any glazing in the door shall be beveled at not less than 45 degrees.
(ar) This is a department rule in addition to the requirements in ASME A18.1 section 2.1.2.1: Where the platform enclosure extends less than 79 inches above the platform, the horizontal clearance between the platform enclosure on a side not containing an entrance and the adjacent runway enclosure wall or the vertical surface of the machine tower may not exceed 4 inches. The horizontal clearance between the platform enclosure and the runway enclosure walls on either side of the machine tower may not exceed 12 inches. These maximum clearances do not apply to spaces above the machine tower or to any point more than 42 inches above the top landing.
(b) This is a department rule in addition to the requirements in ASME A18.1 section 2.1.2.3: Where the lift side of the door and sill present a smooth surface located not closer than 3/8 inch and not more than 3/4 inch from the access edge of the platform floor, the clearance between the edge of the platform floor and the glazing in a fire-rated runway door shall be not more than 1 1/4 inches. The shear condition at the top of any glazing in the door shall be beveled at not less than 45 degrees.
(3) RUNWAY ENCLOSURE NOT PROVIDED. This is a department rule in addition to the requirements in ASME A18.1 section 2.1.3: Lifts without runway enclosures shall meet the building code, specifically for any unguarded space below the lift platform of more than 27 inches above the floor.
(3m) RELOCATABLE LIFTS. The requirements of ASME A18.1 section 2.1.5 are not included as part of this chapter.
(4) RAMPS.
(a) Substitute the following wording for the requirements in ASME A18.1 section 2.1.7.1: Ramps, where provided, shall be in accordance with the building code.

Note: A surface steeper than 1:48 within the wheelchair-maneuvering clearances that are required by the building code at a lift entrance are also required by the building code to have a power-opening entrance, with clearances to the lift call and door-opener button also meeting the building code.

(b) Substitute the following wording for the requirements in the last sentence and pars. (a) to (e) of ASME A18.1 section 2.1.7.2: When in use, the inclination of retractable ramps shall be in accordance with the building code.
(5) SIZE OF END ENTRANCE PLATFORMS. Substitute the following wording for the requirements in ASME A18.1 section 2.6.5: Platform lifts shall have a minimum clear width of 36 inches and a minimum clear length of 54 inches. For lifts complying with ASME A18.1 sections 2.1.1, 2.1.2, and 2.1.3, the net inside floor area may not exceed 18 square feet. For lifts complying with ASME A18.1 section 2.1.4, the net inside floor area may not exceed 25 square feet. Platform lift controls and the required grab rail or grab bar may not project more than 4 inches from the platform side wall measured between a minimum of 30 inches to a maximum of 48 inches above the platform floor.
(6) ILLUMINATION. Substitute the following wording for the requirements in ASME A18.1 section 2.6.6.3: An auxiliary illumination source shall be provided to give general illumination of not less than 0.2 foot candles on the floor and controls. The auxiliary illumination system shall function according to all of the following:
(a) Activate when normal illumination fails.
(b) Utilize not less than 2 lamps of approximately equal intensity.
(c) Provide illumination of at least 0.2 foot candles for at least 90 minutes if the lift is designed and installed to operate normally for at least 2 cycles up and down after the lift's main power fails.
(d) Provide illumination of at least 0.2 foot candles for at least 4 hours if the lift is not designed and installed to operate normally for at least 2 cycles up and down after the lift's main power fails.
(7) LIMITATION ON LOAD SPEED AND TRAVEL. Substitute the following wording for the requirements in the first and second sentences of ASME A18.1 section 2.7.1: Platforms with a floor area of 18 square feet or less shall have a rated load of not less than 750 pounds.
(8) OPERATING DEVICES. Substitute the following wording for the requirements in ASME A18.1 section 2.10.1: Operation of the lift from the landings and platform shall be controlled by continuous-pressure-type switches. The operating devices shall be designed so that both the up and down circuits cannot be operated at the same time.

Note: See the building code for requirements relating to accessible controls, operation, and signage.

(9) MANUAL OPERATION. Substitute the following wording for the requirements in ASME A18.1 section 2.10.10: A vertical platform lift which is not connected to a building's standby or emergency power and which is not equipped with rechargeable battery power capable of cycling the lift under full load for at least 2 cycles after normal building power is removed shall be provided with a means to manually raise or lower the platform to a landing. The means shall be operable only by lift personnel, and from a landing, without working directly over the platform.
(10) EMERGENCY SIGNALS.
(am) These are department rules in addition to the requirements in ASME A18.1 sections 2.11, 2.11.1, and 2.11.3:
1. A vertical platform lift installed outdoors shall have an emergency signaling device provided in accordance with the requirements in ASME A18.1 sections 2.11.1 and 2.11.3, with a sound pressure rating of not less than 80 decibels nor greater than 90 decibels at 10 feet away. The signal shall respond without delay when the switch is activated.
2. A vertical platform lift installed indoors in a building that is staffed 24 hours per day shall have a signaling device provided in accordance with ASME A18.1 sections 2.11.1 and 2.11.3, which is audible at 10 decibels minimum above ambient sound, at a continuously-staffed location. The signal shall respond without delay when the switch is activated.
(bm) Substitute the following wording for the requirements in ASME 18.1 section 2.11.2: A vertical platform lift meeting the requirements in ASME A18.1 sections 2.1.1, 2.1.2, or 2.1.3 that is installed indoors in an area which is not visible to personnel at all times shall have emergency signaling devices provided in accordance with the requirements in ASME A18.1 section 2.11.1 and ASME A17.1 sections 2.27.1.1.1 to 2.27.1.1.3 and 2.27.1.1.5 except "in the elevator" and "in the car" mean "on the platform.

Wis. Admin. Code Department of Safety and Professional Services SPS 318.1802

CR 14-020: cr. Register August 2014 No. 704, eff. 9-1-14.
Amended by, CR 19-118: renum. (2) (a) to (2) (ar), cr. (2) (ag), am. (2) (b), cr. (3m), am. (4) (a), (b), cons. and renum. (5) (intro.) and (a) to (5) and am., r. (5) (b), am. (9), renum. (10) (intro.), (a), (b), (c) to (10) (am) (intro.), 1., 2., (bm) and, as renumbered, am. (10) (am) (intro.), (bm) Register May 2020 No. 773, eff. 6/1/2020