Wis. Admin. Code SPS § SPS 366.0603

Current through May 28, 2024
Section SPS 366.0603 - Smoke alarms

These are department rules in addition to the requirements in IEBC section 603:

(1) No smoke alarm, including an alarm that exists on September 1, 2011, may remain in service for more than that specified by the manufacturer.
(2) The replacement of a smoke alarm that uses a battery as its primary power source shall be a new smoke alarm that complies with UL 217 and either of the following:
(a) The alarm is hardwired in accordance with IBC section 907.2.11.4 and has backup power in accordance with that section.
(b) The alarm uses, as its primary power source, a non-replaceable, non-removable battery that is capable of powering the alarm for at least 10 years.

Wis. Admin. Code Department of Safety and Professional Services § SPS 366.0603

Adopted by, CR 10-103: cr. Register August 2011 No. 668, eff. 9-1-11; CR 16-094: renum. from 366.0503 and am. (intro.) Register April 2018 No. 748, eff. 5/1/2018