Current through May 28, 2024
Section SPS 364.0506 - Commercial kitchen grease ducts and exhaust equipment(2) JOINTS, SEAMS AND PENETRATIONS OF GREASE DUCTS.(a) This is a department alternative to the requirements, but not the exceptions, in IMC section 506.3.2: Joints, seams and penetrations of grease ducts may be made with any other means that provide a liquid-tight seal at 1500oF and that are listed and labeled for the application.(b) This is a department rule in addition to the requirements in IMC section 506.3.2.: Duct joints may also be flanged joints.(c) The requirements of IMC section 506.3.2.5 are not included as part of this chapter.Wis. Admin. Code Department of Safety and Professional Services § SPS 364.0506
CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 06-120: r. (1) and (2) (c), am. (2) (title) and (a), r. and recr. (2) (b), cr. (2) (bm) Register February 2008 No. 626, eff. 3-1-08; CR 10-103: renum. (2) (bm) to be (2) (c) and am. Register August 2011 No. 668, eff. 9-1-11.