Current through October 28, 2024
Section SPS 362.1010 - Doors, gates, and turnstiles(1) CLEAR DOOR OPENINGS FOR NONACCESSIBLE STALLS. This is a department exception to the requirements in IBC section 1010.1.1: The clear door opening for a nonaccessible toilet stall, shower stall, or other similar compartment, may be less than 32-inches wide.(2) DOOR ARRANGEMENT. This is a department exception to the requirements in IBC section 1010.1.8: Where maneuvering space is provided between the doors in accordance with IBC section 1101.2 such that use by an individual in a wheelchair will not block the operation of the doors.(3) PANIC AND FIRE EXIT HARDWARE. Substitute the following wording for the requirements relating to electrical rooms in IBC section 1010.1.10:(a) An electrical room that contains equipment rated 800 amperes or more, and contains overcurrent devices, switching devices, or control devices, and contains a personnel door intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door shall be equipped with panic hardware or fire exit hardware and open in the direction of egress.(b) An electrical room that is over 6 feet wide and contains equipment rated 1,200 amperes or more, and contains overcurrent devices, switching devices or control devices, and contains an exit or exit access door, the door shall be equipped with panic hardware or fire exit hardware and open in the direction of egress.Wis. Admin. Code Department of Safety and Professional Services SPS 362.1010
Adopted by, CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 10-103: am. (2) Register August 2011 No. 668, eff. 9-1-11; CR 16-094: renum. 362.1008 to 362.1010 and am. (1), (2), cr. (3), Register April 2018 No. 748, eff. 5/1/2018