Wis. Admin. Code Department of Safety and Professional Services SPS 362.0705

Current through September 30, 2024
Section SPS 362.0705 - Exterior Walls
(1) CONNECTIONS BETWEEN BUILDINGS. This is a department exception to the requirements in IBC section 705.1: This section does not apply to connections between buildings that are in compliance with IBC section 3104.
(2) PROJECTIONS. Substitute Table 362.0705-2 for IBC Table 705.2.

Table 362.0705-2

Minimum Distance of Projection

Fire Separation Distance (FSD)

Minimum Distance

From Line

Used to Determine FSD

0 feet to 2 feet

Projections not permitted

Greater than 2 feet to 3 feet

24 inches

Greater than 3 feet to less than 30 feet

24 inches plus 8 inches for every foot of FSD beyond 3 feet or fraction thereof

30 feet or greater

40 inches

Wis. Admin. Code Department of Safety and Professional Services SPS 362.0705

CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 10-103: renum. from Comm 62.0704 and am. Register August 2011 No. 668, eff. 9-1-11.
Amended by, CR 16-094: renum. 362.0705 to 362.0705 (1), cr. (2) and Table, Register April 2018 No. 748, eff. 5/1/2018