Wis. Admin. Code Department of Safety and Professional Services SPS 377.12

Current through August 26, 2024
Section SPS 377.12 - Automatic smoke outlet

Where a proscenium curtain is required or provided, the stage shall be provided with one or more automatic smoke outlets, constructed of metal or other incombustible material, placed near the center and above the highest part of the stage, and having a combined area equal to not less than 8% of the area of the stage floor. Vertical louver openings shall be placed not less than 3 feet above the roof and shall be not less than twice the area of the shaft. The smoke outlet shall be designed and constructed so as to open by gravity, and so as to effectively overcome the effects of neglect, rust, dirt, frost, snow, heat, twisting, or warping of the framework. The louvers or dampers, in the openings shall be held closed by cotton or hemp cords running to the stage floor close to each stage door. Fusible links, or other approved heat release devices, shall be inserted in each cord near the outlets.

Wis. Admin. Code Department of Safety and Professional Services SPS 377.12

1-2-56; renum., Register, September, 1974, No. 225, eff. 10-1-74.