Wis. Admin. Code Department of Safety and Professional Services SPS 376.13

Current through August 26, 2024
Section SPS 376.13 - Heating plants
(1) Any new installation or replacement of a heating boiler, furnace or power boiler together with the breeching and fuel room in buildings of this classification shall be enclosed in a separate room having a 2-hour fire-resistive floor. The walls and ceiling shall be of one-hour fire-resistive construction or better. All openings shall be protected with self closing fire-resistive doors.
(2) Space heaters, suspended furnaces and suspended direct fired unit heaters fired with various fuels may be used without an enclosure where approved by the department. Where suspended furnaces and direct-fired unit heaters are used without an enclosure, all such units shall be located at least 7 feet above the floor.

Wis. Admin. Code Department of Safety and Professional Services SPS 376.13

1-2-56; renum. and am., Register, September, 1974, No. 225, eff. 10-1-74.