Wis. Admin. Code Department of Safety and Professional Services SPS 376.03

Current through August 26, 2024
Section SPS 376.03 - Stairways
(1) Every stairway in buildings more than 3 stories in height shall be enclosed with not less than one-hour fire-resistive partitions and fire-resistive doors. (ss. SPS 375.08, 375.09)
(1m) Monumental stairs leading from the street floor to the second floor or to a basement used for commercial purposes need not be enclosed provided they are effectively cut off at the second floor and basement by fire-resistive partitions, as specified above.
(2) Outside stairways heretofore constructed on buildings not more than 2 stories in height will be accepted if properly constructed and in good condition.
(3) Existing inside stairways at a steeper angle than 45º with the horizontal, or less than 3 feet in width, will not be accepted as exits.
(4) All stairways and steps of more than 3 risers shall have at least one handrail. Stairways and steps which are 5 feet or more in width, or which are open on both sides, shall have a handrail on each side. Rails shall be not less than 2 feet 6 inches vertically above nose of treads or 3 feet above platform.

Wis. Admin. Code Department of Safety and Professional Services SPS 376.03

1-2-56; renum. and am., Register, September, 1974, No. 225, eff. 10-1-74; correction made under s. 13.93(2m) (b) 7, Stats., Register, June, 1995, No. 474; correction in (1) made under s. 13.92(4) (b) 7, Stats., Register December 2011 No. 672.