Wis. Admin. Code Department of Natural Resources NR 811.82

Current through September 30, 2024
Section NR 811.82 - Storage requirements

Elevated storage is not required for a boosted pressure zone where the primary pressure zone can provide minimum pressures of 35 psi at street elevation in all areas of the boosted zone. Elevated storage facilities shall be provided for a boosted pressure zone serving more than 50 living units in any of the following situations:

(1) If the primary pressure zone cannot maintain pressures of 3 psi or greater at street elevation in all areas served by the booster pumps including situations where emergency power is provided.
(2) If the primary pressure zone provides pressures of 3 to 35 psi at street elevation in all areas served by the booster pumps and an emergency power source is not provided for the booster station.

Wis. Admin. Code Department of Natural Resources NR 811.82

CR 09-073: cr. Register November 2010 No. 659, eff. 12-1-10.