Wis. Admin. Code NR § 810.59

Current through May 28, 2024
Section NR 810.59 - CT table for Giardia lamblia when using ozone

CT Values for Inactivation of Giardia lamblia Cysts by Ozone

Inactivation Temperature, °C
[LESS than]=1 5 10 15 20 25
0.5-log 0.48 0.32 0.23 0.16 0.12 0.08
1-log 0.97 0.63 0.48 0.32 0.24 0.16
1.5-log 1.5 0.95 0.72 0.48 0.36 0.24
2-log 1.9 1.3 0.95 0.63 0.48 0.32
2.5-log 2.4 1.6 1.2 0.79 0.60 0.40
3-log 2.9 1.9 1.43 0.95 0.72 0.48

Wis. Admin. Code Department of Natural Resources § NR 810.59

CR 09-073: cr. Register November 2010 No. 659, eff. 12-1-10.