Wis. Admin. Code NR § 810.57

Current through May 28, 2024
Section NR 810.57 - CT table for Giardia lamblia when using chloramines

CT Values for Inactivation of Giardia lamblia Cysts by Chloramine pH 6-9

Inactivation Temperature, °C
[LESS than]= 1 5 10 15 20 25
0.5-log 635 365 310 250 185 125
1-log 1,270 736 615 500 370 250
1.5-log 1,900 1,100 930 750 550 375
2-log 2,535 1,470 1,230 1,000 735 500
2.5-log 3,170 1,830 1,540 1,250 915 625
3-log 3,800 2,200 1,850 1,500 1,100 750

Wis. Admin. Code Department of Natural Resources § NR 810.57

CR 09-073: cr. Register November 2010 No. 659, eff. 12-1-10.