CT Values for Inactivation of Giardia lamblia Cysts by Chlorine Dioxide
Inactivation | Temperature, °C | |||||
[LESS than]=1 | 5 | 10 | 15 | 20 | 25 | |
0.5-log | 10 | 4.3 | 4 | 3.2 | 2.5 | 2 |
1-log | 21 | 8.7 | 7.7 | 6.3 | 5 | 3.7 |
1.5-log | 32 | 13 | 12 | 10 | 7.5 | 5.5 |
2-log | 42 | 17 | 15 | 13 | 10 | 7.3 |
2.5-log | 52 | 22 | 19 | 16 | 13 | 9 |
3-log | 63 | 26 | 23 | 19 | 15 | 11 |
Wis. Admin. Code Department of Natural Resources NR 810.54