If the system bin classification is: | And the system uses the following filtration treatment in full compliance with s. NR 810.29 (as appli-cable), then the additional Cryptosporidium treatment requirements are: | |||||
Conventional filtration treatment (including softening) | Direct filtration | Slow sand or diatomaceous earth filtration | Alternative filtration technologies including membrane filtration | |||
Bin 1 | No additional treatment | No additional treatment | No additional treatment | No additional treatment. | ||
Bin 2 | 1-log treatment | 1.5-log treatment | 1-log treatment | As determined by the department such that the total Cryptosporid-ium removal and inactivation is at least 4.0-log. | ||
Bin 3 | 2-log treatment | 2.5-log treatment | 2-log treatment | As determined by the department such that the total Cryptosporid-ium removal and inactivation is at least 5.0-log. | ||
Bin 4 | 2.5-log treatment | 3-log treatment | 2.5-log treatment | As determined by the department such that the total Cryptosporid-ium removal and inactivation is at least 5.5-log. | ||
Wis. Admin. Code Department of Natural Resources § NR 810.35