Wis. Admin. Code ATCP § ATCP 76.15

Current through December 30, 2024
Section ATCP 76.15 - Alternative or supplemental disinfection systems

Any one of the following alternative or supplemental systems may be added to a pool if an automated disinfection system is in place and on line to maintain the disinfectant or sanitizer residuals pursuant to s. ATCP 76.14 Table A. Pf

(1) CHLORINE GENERATORS.
(a)NSF 50. Chlorine generators, including salt systems, shall be certified and installed to NSF 50 and manufacturer instructions. Pf
(b)Disinfectant system on line. An additional disinfection system shall remain on line and able to automatically provide the capacity to superchlorinate the water and maintain the required sanitizer residual. P
(2) OZONE GENERATORS.
(a)Maximum concentration. Ozone generators shall provide a concentration of ozone in the return line to the pool not to exceed 0.1 mg/L. P
(b)Electrically interlocked. The ozone generator shall be electrically interlocked with the recirculation pump to prevent the feeding of ozone when the recirculation pump is not operating. A flow sensor controller may also be used to turn off the feeder when flow is interrupted. P
(c)Maximum ambient ozone level. Off-gassing of ozone may not result in ozone levels in the equipment room or pool area exceeding 0.1 ppm. P
(3) ULTRAVIOLET LIGHT. Ultraviolet light units shall be certified to NSF 50, and tested and approved for use in water disinfection systems and installed pursuant to NSF 50 requirements. P
(4) OTHER TECHNOLOGIES. Other technologies that inactivate or kill pathogens shall be certified and installed pursuant to NSF 50, manufacturer instructions, and have an EPA registration number, if applicable. P

Wis. Admin. Code Department of Agriculture, Trade and Consumer Protection ATCP 76.15

Renumbered from DHS 172.15 Register June 2016 No. 726; correction in (intro.) made under s. 13.92(4) (b) 7, Stats., Register June 2016 No. 726, eff. 7/1/2016
Adopted by, CR 22-021: cr. Register June 2023 No. 810, eff. 9/24/2023

This section is created eff. 9-24-23 by CR 22-021.