W. Va. Code R. agency 64, tit. 64, ser. 64-47, tbl. 64-47G

Current through Register Vol. XLI, No. 45, November 8, 2024
Table 64-47G - PERMISSIBLE AERATION TANK CAPACITIES AND LOADINGS

Process

Aeration Tank Organic Loading--lb.BOD5***/day per 1000 cu. ft.

F/M Ratio lb.BOD5***/day per lb.MLVSS

MLSS*

mg/litter

Conventional step aeration complete mix

40

0.2-0.5

1000-3000

Contact stabilization

50**

0.2-0.6

1000-3000

Extended aeration 3000-5000

oxidation ditch

15

0.05-0.1

*MLSS values are dependent upon the surface area provided for sedimentation and the rate of sludge return as well as the aeration process.

**Total aeration capacity, includes both contact and reaeration capacities. Normally the contact zone equals 30 to 35% of the total aeration capacity.

***BOD5 or BOD5is the scientific method used to accurately measure dissolved oxygen consumption, by comparison of dissolved oxygen in a sample at the beginning and at the end of a five-day period.

W. Va. Code R. agency 64, tit. 64, ser. 64-47, tbl. 64-47G