W. Va. Code R. § 179-10-15

Current through Register Vol. XLI, No. 36, September 6, 2024
Section 179-10-15 - Physical and environment controls for equipment
15.1. An interactive gaming system and its associated communications systems must be located in facilities that provide physical protection against damage from fire, flood, hurricane, earthquake, and other forms of natural or manmade disaster by utilizing and implementing, at a minimum, the following measures:
15.1.1. Security perimeters (barriers such as walls, card controlled entry gates or manned reception desks) must be used to protect areas that contain interactive gaming systems components.
15.1.2. Protection of secure areas by appropriate entry controls to ensure that access is restricted to authorized personnel only;
15.1.3. Record of all access in a secure log that is available for inspection by Director;
15.1.4. An intrusion detection system in secure areas. Attempts at unauthorized access must be logged;
15.1.5. Locate interactive gaming servers in server rooms that prohibit unauthorized access;
15.1.6. House interactive gaming servers in racks located within a secure area;
15.1.7. Interactive gaming system components shall include all of the following minimum utility support:
15.1.7.a. Adequate power;
15.1.7.b. Uninterruptible power to support operations in the event of a power failure;
15.1.7.c. Adequate cooling for the equipment housed in the server room;
15.1.7.d. Protection from interception of communications or damage for power and telecommunications cabling carrying data or supporting information services; and
15.1.7.e. Adequate fire protection for the interactive gaming system components housed in the server room.

W. Va. Code R. § 179-10-15