Wash. Admin. Code § 51-51-2904

Current through Register Vol. 24-17, September 1, 2024
Section 51-51-2904 - Section 2904-Dwelling unit fire-sprinkler systems
P2904.1.1Required sprinkler locations. Sprinklers shall be installed to protect all areas of a dwelling unit.

EXCEPTIONS:

1. Uninhabitable attics, crawl spaces and normally unoccupied concealed spaces that do not contain fuel-fired appliances do not require sprinklers. In uninhabitable attics, crawl spaces and normally unoccupied concealed spaces that contain fuel-fired equipment, a sprinkler shall be installed above the equipment; however, sprinklers shall not be required in the remainder of the space.

2. Clothes closets, linen closets and pantries not exceeding 24 square feet (2.2 m2) in area, with the smallest dimension not greater than 3 feet (915 mm) and having wall and ceiling surfaces of gypsum board.

3. Bathrooms not more than 55 square feet (5.1 m2) in area.

4. Garages; carports; exterior porches; unheated entry areas, such as mud rooms, that are adjacent to an exterior door; and similar areas.

Wash. Admin. Code § 51-51-2904

Adopted by WSR 20-12-027, Filed 5/27/2020, effective 7/1/2020
Amended by WSR 23-23-104, Filed 11/15/2023, effective 3/16/2024