Table 706.4
Fire Wall Fire-resistance Ratings
GROUP | FIRE-RESISTANCE RATING (hours) |
A, B, E, H-4, I, R-1, R-2, U | 3a |
F-1, H-3b, H-5, M, S-1 | 3 |
H-1, H-2 | 4b |
F-2, S-2, R-3, R-4 | 2 |
a In Type II, III, IV, or V construction, walls shall be permitted to have a 2-hour fire-resistance rating.
b For Group H-1, H-2, or H-3 buildings, also see Sections 415.7 and 415.8.
Wash. Admin. Code § 51-50-0706
Reviser's note: The bracketed material preceding the section above was supplied by the code reviser's office.