Table 509.1
Incidental Uses
Room or Area | Separation and/or Protection |
Dry type transformers over 112.5 kVA and required to be in a fire resistant room per NEC (NFPA 70) Section 450.21 (B)1 | 1 hour or provide automatic sprinkler system |
1 Dry type transformers rated over 35,000 volts and oil-insulated transformers shall be installed in a transformer vault complying with NFPA 70.
(Remainder of table unchanged)
Wash. Admin. Code § 51-50-0509
Statutory Authority: RCW 19.27.031 and chapters 19.27 and 34.05 RCW. 13-04-067, § 51-50-0509, filed 2/1/13, effective 7/1/13. Statutory Authority: RCW 19.27.031 and 19.27.074. 10-03-097, § 51-50-0509, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.074, 19.27.020, and chapters 70.92, 19.27, and 34.05 RCW. 07-01-091, § 51-50-0509, filed 12/19/06, effective 7/1/07.