Section 51-11R-40351 - Table R403.6.1-Mechanical ventilation system fan efficacy

TABLE R403.6.1 WHOLE HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACYa

System Type

Air Flow Rate (cfm)

Minimum Efficacy (cfm/watt)

HRV, ERV or balanced

Any

1.2

Range hoods

Any

2.8

In-line supply or exhaust fan

Any

3.8

Other exhaust fan

<90

2.8

Other exhaust fan

[GREATER THAN EQUAL TO]90

3.5

For SI: 1 cfm = 28.3 L/min.

a. Design outdoor or exhausted airflow rates/watt of fan used.