Heated water circulation systems shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be in a location with access. Manual controls shall be in a location with ready access.
EXCEPTION: | Pipe insulation is permitted to be discontinuous where it passes through studs, joists or other structural members and where the insulated pipes pass other piping, conduit or vents, provided the insulation is installed tight to each obstruction. |
EXCEPTIONS: | 1. Where the hot water system efficiency is greater than or equal to 2.0 UEF. 2. Tankless water heaters. 3. Gas heat pump water heaters intended for exterior installation. 4. Atmospheric vented gas water heaters. |
Heat pumps used for water heating and having supplementary water heating equipment shall have controls that limit supplementary water heating equipment operation to only those times when one of the following applies:
EXCEPTION: | Heat trace temperature maintenance systems, provided the system capacity does not exceed the capacity of the heat pump water heating system. |
Wash. Admin. Code § 51-11R-40340