Wash. Admin. Code § 51-11R-40315

Current through Register Vol. 24-21, November 1, 2024
Section 51-11R-40315 - Section R4032-Hot water boiler

R403.2 Hot water boiler temperature reset. The manufacturer shall configure each gas, oil, and electric boiler (other than a boiler equipped with a tankless domestic water heating coil) with an automatic means of adjusting the water temperature supplied by the boiler to ensure incremental change of the inferred heat load will cause an incremental change in the temperature of the water supplied by the boiler. This can be accomplished with outdoor reset, indoor reset, or water temperature sensing.

Wash. Admin. Code § 51-11R-40315

Adopted by WSR 16-02-127, Filed 1/6/2016, effective 7/1/2016
Amended by WSR 23-02-060, Filed 1/3/2023, effective 7/1/2023