A108.1 General. Tables A108.1(1) and A108.1(2) list effective air change rates and heat capacities for heat loss due to infiltration for Single-Family Residential.
The estimated seasonal average infiltration rate in air changes per hour (ACH) is given for standard air-leakage control (see Section R402.4 for air leakage requirements for Single-Family Residential). The effective air change rate shall be used in calculations for compliance under either the Component Performance or Systems Analysis approaches.
Heat loss due to infiltration shall be computed using the following equation:
Qinfil | = | ACHeff * HCP |
Where: | ||
Qinfil | = | Heat loss due to air infiltration. |
ACHeff | = | The effective air infiltration rate in Table A108.1(1) |
HCP | = | The Heat Capacity Density Product for the appropriate elevation or climate zone as given below. |
Table A108.1(1) Assumed Effective Air Changes per Hour
Air-Leakage | Air Changes per Hour | |
Control Package | Natural | Effective |
Standard | 0.35 | 0.35 |
Table A108.1(2) Default Heat Capacity/Density Product for Air
Zone | Average Elevation | Heat Capacity/Density |
1 | Mean Sea Level | 0.0180 Btu/h . °F |
2 | 2000 | 0.0168 Btu/h . °F |
3 | 3000 | 0.0162 Btu/h . °F |