Wash. Admin. Code § 51-11C-40511

Current through Register Vol. 24-23, December 1, 2024
Section 51-11C-40511 - Section C405.11-Voltage drop
C405.11Voltage drop. The total voltage drop across the combination of customer-owned service conductors, feeder conductors and branch circuit conductors shall not exceed five percent.

Wash. Admin. Code § 51-11C-40511

Reserved by WSR 16-03-072, Filed 1/19/2016, effective 7/1/2016
Amended by WSR 16-24-070, Filed 12/6/2016, effective 5/1/2017
Amended by WSR 19-24-040, Filed 11/26/2019, effective 7/1/2020
Amended by WSR 20-21-080, Filed 10/19/2020, effective 2/1/2021
Amended by WSR 22-14-091, Filed 7/1/2022, effective 7/1/2023

Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. 13-04-056, § 51-11C-40511, filed 2/1/13, effective 7/1/13.