Wash. Admin. Code § 51-11C-40394

Current through Register Vol. 24-21, November 1, 2024
Section 51-11C-40394 - Section C403.13-Dehumidification for plant growth
C403.13Dehumidification in spaces for plant growth and maintenance. Equipment that dehumidifies building spaces used for plant growth and maintenance shall be one of the following:
1.Stand-alone dehumidifiers that meet the following minimum integrated energy factors as measured by the test conditions in Appendix X1 to Subpart B of 10 C.F.R. Part 430 :
1.1. Minimum integrated energy factor of 1.77 L/kWh for product case volumes of 8.0 cubic feet or less;
1.2. Minimum integrated energy factor of 2.41 L/kWh for product case volumes greater than 8.0 cubic feet;
2.Integrated HVAC system including, but not limited to, heat pump technology, with on-site heat recovery designed to fulfill at least 75 percent of the annual energy for dehumidification reheat;
3. Chilled water system including, but not limited to, heat pump technology, with on-site heat recovery designed to fulfill at least 75 percent of the annual energy for dehumidification reheat; or
4. Solid or liquid desiccant dehumidification system for system designs that require dewpoint of 50°F (10°C) or less.
C403.14Commissioning. Mechanical systems shall be commissioned in accordance with Section C408.

Wash. Admin. Code § 51-11C-40394

Adopted by WSR 22-14-091, Filed 7/1/2022, effective 7/1/2023