EXCEPTION : | The use of mixed air temperature limit control shall be permitted for systems that are both controlled from space temperature (such as single zone systems) and having cooling capacity less than 65,000 Btu/h. |
Table C403.5.3.3 High-Limit Shutoff Control Setting for Air Economizersb
Device Type | Required High Limit (Economizer off when): | Required High Limit For Cycling Fansc (Economizer off when): | ||
Equation | Description | Equation | Description | Description |
Fixed dry-bulb | TOA75°F | Outdoor air temperature exceeds 75°F | TOA70°F | Outdoor air temperature exceeds 70°F |
Differential dry-bulb | Toa [GREATER THAN] Tra | Outdoor air temperature exceeds return air temperature | TOA [GREATER THAN] (TRA- 5) | Outdoor air temperature exceeds return air temperature - 5 |
Fixed enthalpy with fixed dry-bulb temperatures | hOA [GREATER THAN] 28 Btu/lba or TOA[GREATER THAN] 75°F | Outdoor air enthalpy exceeds 28 Btu/lb of dry aira or outdoor air temperature exceeds 75°F | hOA [GREATER THAN] 26 Btu/lba or TOA[GREATER THAN] 70°F | Outdoor air enthalpy exceeds 26 Btu/lb of dry aird or outdoor air temperature exceeds 70°F |
Differential enthalpy with fixed dry-bulb temperature | hOA[GREATER THAN] hRA or TOA [GREATER THAN] 75°F | Outdoor air enthalpy exceeds return air enthalpy or outdoor air temperature exceeds 75°F | hOA [GREATER THAN] (hRA - 2) or TOA [GREATER THAN] 70°F | Outdoor air enthalpy exceeds return air enthalpy or outdoor air temperature exceeds 70°F |
For SI: °C = (°F - 32) × 5/9, 1 Btu/lb = 2.33 kJ/kg.
aAt altitudes substantially different than sea level, the fixed enthalpy limit shall be set to the enthalpy value at 75°F and 50 percent relative humidity. As an example, at approximately 6,000 feet elevation the fixed enthalpy limit is approximately 30.7 Btu/lb.
bDevices with selectable setpoints shall be capable of being set to within 2°F and 2 Btu/lb of the setpoint listed.
cWhere fans cycle on only to provide heating and cooling, limits are adjusted lower to compensate for fan energy use in economizer mode.
dFor cycling fans at altitudes substantially different than sea level, the fixed enthalpy limit shall be set to the enthalpy value at 70°F and 50 percent relative humidity.
Wash. Admin. Code § 51-11C-40353