Section 51-11C-40346 - Section C403.4.6-Variable flow controls
C403.4.6Variable flow controls. Individual pumps required by this code to have variable speed control shall be controlled in one of the following manners:
1. For systems having a combined pump motor horsepower less than or equal to 20 hp (15 kW) and without direct digital control of individual coils, pump speed shall be a function of either:
1.1. Required differential pressure; or
1.2. Reset directly based on zone hydronic demand, or other zone load indicators; or
1.3. Reset directly based on pump power and pump differential pressure; or
1.4. Reset directly by an integral controller based on the relationship between variable speed controller frequency and power.
2. For systems having a combined pump motor horsepower that exceeds 20 hp (15 kW) or smaller systems with direct digital control, pump speed shall be a function of either:
2.1. The static pressure set point as reset based on the valve requiring the most pressure; or
2.2. Directly controlled based on zone hydronic demand; or
2.3.Reset directly by an integral controller based on the relationship between variable speed controller frequency and power.