Section 51-11C-40333 - Section C403.3.3-Hot gas bypassC403.3.3Hot gas bypass limitation. Cooling systems shall not use hot gas bypass or other evaporator pressure control systems unless the system is designed with multiple steps of unloading or continuous capacity modulation. The capacity of the hot gas bypass shall be limited as indicated in Table C403.3.3, as limited by Section C403.5.1. Table C403.3.3
Maximum Hot Gas Bypass Capacity
Rated Capacity | Maximum Hot Gas BypassCapacity (% of totalcapacity) |
[LESS THAN EQUAL TO] 240,000 Btu/h | 50 |
[GREATER THAN] 240,000 Btu/h | 25 |
For SI: 1 British thermal unit per hour = 0.2931 W.
Wash. Admin. Code § 51-11C-40333
Adopted by WSR 16-03-072, Filed 1/19/2016, effective 7/1/2016Amended by WSR 19-24-040, Filed 11/26/2019, effective 7/1/2020Amended by WSR 20-21-080, Filed 10/19/2020, effective 2/1/2021