Wash. Admin. Code § 51-11C-403327

Current through Register Vol. 24-21, November 1, 2024
Section 51-11C-403327 - Table C403.3.2(7)-Heat rejection equipment-Minimum efficiency requirements

Table C403.3.2(7)

Heat Rejection Equipment-Minimum Efficiency Requirementsi

Equipment Typea

Total System Heat Rejection Capacity at Rated Conditions

Subcategory or Rating Conditionh

Performance Requiredb,c,d,f,g

Test Procedurea,e

Propeller or axial fan open-circuit cooling towers

All

95°F Entering Water

85°F Leaving Water

75°F Entering wb

[GREATER THAN EQUAL TO] 40.2 gpm/hp

CTI ATC-105 and CTI STD-201 RS

Centrifugal fan open circuit cooling towers

All

95°F Entering Water

85°F Leaving Water

75°F Entering wb

[GREATER THAN EQUAL TO] 20.0 gpm/hp

CTI ATC-105 and CTI STD-201 RS

Propeller or axial fan closed-circuit cooling towers

All

102°F Entering Water

90°F Leaving Water

75°F Entering wb

[GREATER THAN EQUAL TO] 16.1 gpm/hp

CTI ATC-105S

and CTI STD-201 RS

Centrifugal closed-circuit cooling towers

All

102°F Entering Water

90°F Leaving Water

75°F Entering wb

[GREATER THAN EQUAL TO] 7.0 gpm/hp

CTI ATC-105S

and CTI STD-201 RS

Propeller or axial fan dry coolers (air-cooled fluid coolers)

All

115°F Entering Water

105°F Leaving Water

95°F Entering wb

[GREATER THAN EQUAL TO] 4.5 gpm/hp

CTI ATC-106

Propeller or axial fan evaporative condensers

All

R-448A Test Fluid

165°F Entering Gas Temperature

105°F Condensing Temperature

75°F Entering wb

[GREATER THAN EQUAL TO] 160,000 Btu/h · hp

CTI ATC-106

Propeller or axial fan evaporative condensers

All

Ammonia Test Fluid

140°F Entering Gas Temperature

96.3°F Condensing Temperature

75°F Entering wb

[GREATER THAN EQUAL TO] 134,000 Btu/h · hp

CTI ATC-106

Centrifugal fan evaporative condensers

All

R-448A Test Fluid

165°F Entering Gas Temperature

105°F Condensing Temperature

75°F Entering wb

[GREATER THAN EQUAL TO] 137,000 Btu/h · hp

CTI ATC-106

Centrifugal fan evaporative condensers

All

Ammonia Test Fluid

140°F Entering Gas Temperature

96.3°F Condensing Temperature

75°F Entering wb

[GREATER THAN EQUAL TO] 110,000 Btu/h · hp

CTI ATC-106

Air cooled condensers

All

125°F Condensing Temperature

R-22 Test Fluid

190°F Entering Gas Temperature

15°F Subcooling

95°F Entering db

[GREATER THAN EQUAL TO] 176,000 Btu/h · hp

AHRI 460

For SI: °C = [(°F) - 32]/1.8, L/s · kW = (gpm/hp)/(11.83), COP = (Btu/h · hp)/(2550.7).

db = dry-bulb temperature, °F.

wb = wet-bulb temperature, °F.

a Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.

b For purposes of this table, open-circuit cooling tower performance is defined as the water-flow rating of the tower at the thermal rating condition listed in the table divided by the fan motor nameplate power.

c For purposes of this table, closed-circuit cooling tower performance is defined as the water-flow rating of the tower at the thermal rating condition divided by the sum of the fan motor nameplate power and the integral spray pump motor nameplate power.

d For purposes of this table, dry-cooler performance is defined as the process water-flow rating of the unit at the thermal rating condition listed in the table divided by the total fan motor nameplate power of the unit, and air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the total fan motor nameplate power of the unit.

e The efficiencies and test procedures for both open- and closed-circuit cooling towers are not applicable to hybrid cooling towers that contain a combination of separate wet and dry heat exchange sections. The certification requirements do not apply to field-erected cooling towers.

f All cooling towers shall comply with the minimum efficiency listed in the table for that specific type of tower with the capacity effect of any project-specific accessories and/or options included in the capacity of the cooling tower.

g For purposes of this table, evaporative condenser performance is defined as the heat rejected at the specified rating condition in the table, divided by the sum of the fan motor nameplate power and the integral spray pump nameplate power.

h Requirements for evaporative condensers are listed with ammonia (R-717) and R-448A as test fluids in the table. Evaporative condensers intended for use with halocarbon refrigerants other than R-448A must meet the minimum efficiency requirements listed above with R-448A as the test fluid. For ammonia, the condensing temperature is defined as the saturation temperature corresponding to the refrigerant pressure at the condenser entrance. For R-448A, which is a zeotropic refrigerant, the condensing temperature is defined as the arithmetic average of the dew point and the bubble point temperatures corresponding to the refrigerant pressure at the condenser entrance.

i This table is a replica of ASHRAE 90.1 Table 6.8.1-7 Performance Requirements for Heat Rejection Equipment-Minimum Efficiency Requirements.

Wash. Admin. Code § 51-11C-403327

Adopted by WSR 22-14-091, Filed 7/1/2022, effective 7/1/2023